144
144 EN
MANUAL ELDES ESIM264 V3.1
32.9.2. PLACEMENT
1. Install the wireless smoke detector as close to the center of the ceiling as possible. If this is not practical, mount no closer than 10
centimeters from a wall or corner. Also, if local codes allow, install wireless smoke detectors on walls, between 10 and 30 centimeters
from ceiling/wall intersections.
2. Install a minimum of two wireless smoke detectors in every house, no matter how small the house is.
3. Install a wireless smoke detector in each room that is divided by a partial wall (either coming down from the ceiling at least 20 centim-
eters, or coming up from the oor).
4. Install a wireless smoke detector in lived-in attics or attics which ho use electrical equipment like furnaces, air conditioners, or heaters.
NOTE: For best protection we recommend that you install a wireless smoke detector in every room.
Recommended EWF1 placement locations
Ceiling
Wall
HORIZONTAL DISTANCE
ANYWHERE
IN THIS AREA
NEVER
HERE
Acceptable
here
0,9 m (3 ft) 0,9 m (3 ft)
Top of detector
acceptable here
(0,1 m)
(0,1 m)
Max.
(0,3 m)
Max.
85
NOTE: Measurements shown are to the closest edge of the detector.
Typical Single-Story House
Install a wireless smoke detector on the ceiling or wall inside each bedroom and in the hallway outside each separate sleeping area. If a
bedroom area hallway is more than 9 meters long, install a wireless smoke detector at each end.
If there is a basement: Install a wireless smoke detector on the basement ceiling at the bottom of the stairwell.
Bedroom
Bedroom
Family Room
Living Room
Kitchen
Dining Room
Bedroom
86
LEGEND:
Minimum required smoke
detector locations.
Recommended additional
smoke detector locations