MANUAL ELDES ESIM264 V3.1
12.7. Arm-Disarm by Zone
ARM/
DISARM
ZONE
The Arm-Disarm by Zone feature allows to use a zone for arming and disarming the alarm system when the zone is violated and
restored. The process is performed by providing a low-level pulse for more than 3 seconds into the specied zone. It means that
violating and restoring the zone leads to system arming and by repeating this action the system becomes disarmed. The system
will arm/disarm the partition (-s) that the zone is assigned to. This method can be set up for one on-board zone only.
Set zone for Arm-
Disarm by Zone
method
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → ZONE 1... 12 → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 & on-board zone number:
34 nn #
Value: nn – on-board zone number, range – [01... 12].
Example: 3403#
Cong
Tool
This operation may be carried out from the PC using the ELDES Conguration Tool software.
Disable Arm-Disarm by
Zone method
EKB2
Menu path:
OK → CONFIGURATION → OK → aaaa → OK → ZONES → OK → ARM/DISARM BY ZONE
→ OK → N/A → OK
Value: aaaa – 4-digit administrator password.
EKB3
Enter parameter 34 & parameter status value
34 00 #
Example: 3400#
Cong
Tool
This operation may be carried out from the PC using the ELDES Conguration Tool software.